Submersible MotorsApplication • Installation • Maintenance60 Hz, Single-Phase and Three-Phase Motors2007

Page 2

Application – All MotorsTable 7 lists the approximate head loss due to fl ow between an average length motor and smooth casing or fl ow inducer sleeve.H

Page 3 - Commitment to Quality

Application – All MotorsEXAMPLE: A 6" pump end requiring 39 hp input will pump 124 °F water in an 8" well at a delivery rate of 140 gpm. Fro

Page 4

Application – All MotorsThe primary purpose of grounding the metal drop pipe and/or metal well casing in an installation is safety. It is done to limi

Page 5 - Submersible Motors

Application – Single-Phase MotorsBIAC Switch OperationWhen power is applied the bi-metal switch contacts are closed, so the triac is conducting and en

Page 6

Application – Single-Phase Motors75 °C2 or 3-Wire Cable, 60 Hz (Service Entrance to Motor - Maximum Length In Feet)Lengths in BOLD only meet the US Na

Page 7

Application – Single-Phase Motors3 hp, 230 VSingle-Phase Motor310 ft #6 AWG(41.3% of allowable cable)160 ft #10 AWG(53.3% of allowable cable)Depen

Page 8

Application – Single-Phase Motors(1) Main winding - yellow to black Start winding - yellow to red(2) Y = Yellow lead - line amps B =

Page 9

Application – Single-Phase MotorsTable 14 Single-Phase Motor Fuse SizingTYPEMOTORMODELPREFIXRATINGCIRCUIT BREAKERS OR FUSE AMPS CIRCUIT BREAKERS OR FU

Page 10 - Application – All Motors

Application – Single-Phase MotorsBuck-Boost transformers are power transformers, not control transformers. They may also be used to lower voltage when

Page 11

Application – Three-Phase MotorsContinued on page 17 60 °CMOTOR RATING 60 °C INSULATION - AWG COPPER WIRE SIZE MCM COPPER WIRE SIZEVOLTSHPKW141210864

Page 12

ATTENTION!IMPORTANT INFORMATION FOR INSTALLERS OF THIS EQUIPMENT!THIS EQUIPMENT IS INTENDED FOR INSTALLATION BY TECHNICALLY QUALIFIED PERSONNEL. FAILU

Page 13 - Potential (Voltage) Relays

Application – Three-Phase Motors 60 °CMOTOR RATING 60 °C INSULATION - AWG COPPER WIRE SIZE MCM COPPER WIRE SIZEVOLTSHPKW1412108643210000000000 250 30

Page 14 - Table 11A

Application – Three-Phase Motors 60 °CMOTOR RATING 60 °C INSULATION - AWG COPPER WIRE SIZE MCM COPPER WIRE SIZEVOLTSHPKW1412108643210000000000 250 30

Page 15

Application – Three-Phase MotorsContinued on page 20 75 °CMOTOR RATING 75 °C INSULATION - AWG COPPER WIRE SIZE MCM COPPER WIRE SIZEVOLTSHPKW141210864

Page 16

Application – Three-Phase Motors 75 °CMOTOR RATING 75 °C INSULATION - AWG COPPER WIRE SIZE MCM COPPER WIRE SIZEVOLTSHPKW1412108643210000000000 250 30

Page 17

Application – Three-Phase Motors 75 °CMOTOR RATING 75 °C INSULATION - AWG COPPER WIRE SIZE MCM COPPER WIRE SIZEVOLTSHPKW1412108643210000000000 250 30

Page 18 - Buck-Boost Transformers

Application – Three-Phase MotorsTYPEMOTOR MODEL PREFIXRATING FULL LOAD MAXIMUM (S.F. LOAD)LINE TO LINE RESISTANCE OHMSEFFICIENCY %LOCKED ROTOR AMPSKVA

Page 19 - Continued on page 17

Application – Three-Phase MotorsTable 23 Three-Phase Motor Fuse SizingTYPEMOTORMODELPREFIXRATINGCIRCUIT BREAKERS OR FUSE AMPS CIRCUIT BREAKERS OR FUSE

Page 20 - Continued on page 18

Application – Three-Phase MotorsModel numbers above are for three-lead motors. Six-lead motors with different model numbers have the same running perf

Page 21

Application – Three-Phase MotorsTable 25 Three-Phase Motor Fuse SizingTYPEMOTORMODELPREFIXRATINGCIRCUIT BREAKERS OR FUSE AMPS CIRCUIT BREAKERS OR FUSE

Page 22 - Continued on page 20

Application – Three-Phase MotorsModel numbers above are for three-lead motors. Six-lead motors with different model numbers have the same runningperfo

Page 23 - Continued on page 21

Franklin Electric is committed to provide customers with defect free products through our program of continuous improvement. Quality shall, in every c

Page 24

Application – Three-Phase MotorsTable 27 Three-Phase Motor Fuse SizingTYPEMOTORMODELPREFIXRATINGCIRCUIT BREAKERS OR FUSE AMPS CIRCUIT BREAKERS OR FUSE

Page 25

Application – Three-Phase MotorsOverload Protection of Three-Phase Submersible MotorsThe characteristics of submersible motors are different than stan

Page 26

Application – Three-Phase MotorsFootnotes for Tables 28, 29, and 30 NOTE 1: Furnas intermediate sizes between NEMA starter sizes apply where (1) is sh

Page 27

1. Motor Inspection A. Verify that the model, hp or kW, voltage, phase and hertz on the motor nameplate match the installation requiremen

Page 28

F. Check insulation resistance as pump/motor assembly is lowered into the well. Resistance may drop gradually as more cable enters the w

Page 29

RMA No. _____________ INSTALLER’S NAME ___________________________ OWNER’S NAME _________________________________ADDRESS ____________________________

Page 30

MOTORPUMPPUMPPANELSERVICEENTRANCEPower Supply:Cable: Service Entrance to Control ____________ft_______ AWG/MCM ❑ Copper ❑ Aluminum ❑

Page 31 - Class 10 Protection Required

Submersible Motor Booster Installation RecordDate ______ /______/_______ Filled In By _______________________________ RMA No. _______________Installa

Page 32

Insulation Check:Initial Megs: Motor & Lead Only Black (T1/U1)_________ Yellow (T2/V1)________ Red (T3/W1)_________Installed Megs: Motor, Lead,

Page 33

Application – Three-Phase MotorsAdvance Controls: MDR3 OverloadAEG Series: B17S, B27S, B27-2ABB Type: RVH 40, RVH65, RVP160, T25DU, T25CT, TA25DU

Page 35 - Form No. 2207 8/00

Application – Three-Phase MotorsApplicationsSubMonitor is designed to protect 3-phase pumps/motors with service factor amp ratings (SFA) from 5 to 350

Page 36 - ENTRANCE

Application – Three-Phase MotorsO.L. CONTACTSPRESSURE SWITCH OROTHER CONTROL DEVICECOILL1L2L3FUSESCONTACTSOVERLOADHEATERS AND/ORMOTORSUBTROL PLUSO.L.

Page 37 - Form No. 3655 8/00

Application – Three-Phase Motors 150= 0.02 or 2%A full three-phase supply is recommended for all three-phase motors, consisting of three individual tr

Page 38 - °F or _______ °C

Application – Three-Phase MotorsThree-Phase Motor Lead Identifi cationEach motor lead is numbered with two markers, one near each end. To reverse rotat

Page 39

Application – Three-Phase MotorsAll Franklin three-phase submersible motors are suitable for full-voltage starting. Under this condition the motor spe

Page 40 - Protects Against

Application – Three-Phase MotorsDesign And Operational Requirements1. Non-Vertical Operation: Vertical Shaft-up (0°) to Horizontal (90°) operation is

Page 41 - Three-Phase Starter Diagrams

Application – Three-Phase Motors9. Controls-Soft Starters and VFDs: Reduced voltage starters and variable speed drives (inverter drives) may be used

Page 42 - Three-Phase Power Unbalance

Application – Three-Phase Motors17. Open Atmosphere Booster Pump Systems: When an open booster is placed in a lake, tank, etc. that is open to atmosp

Page 43 - 90° Lead Spacing

Application – Three-Phase MotorsFranklin three-phase submersible motors are operable from variable frequency inverter drives when applied within guide

Page 44 - Inline Booster Pump Systems

Installation – All Motors4” Super Stainless — Dimensions(Standard Water Well)1.508"1.498"1.48"MAX0.030" RMAX0.97"0.79"L*

Page 45 - Pump Load Multiplier

Application – All MotorsStorage ...3Frequency of Starts ...

Page 46

Installation – All Motors4" Motors: 15 to 20 ft-lb (20 to 27 Nm)6" Motors: 50 to 60 ft-lb (68 to 81 Nm)8" Motors with 1-3/16” to 1-5

Page 47

Maintenance – All MotorsSystem TroubleshootingPOSSIBLE CAUSE CHECKING PROCEDURES CORRECTIVE ACTION A. No power or incorrect voltage. Check voltage at

Page 48

Maintenance – All MotorsSystem TroubleshootingPOSSIBLE CAUSE CHECKING PROCEDURES CORRECTIVE ACTION A. Pressure switch. Check switch for welded contac

Page 49 - Installation – All Motors

Maintenance – All MotorsGROUNDL2{TOPOWERSUPPLYBLACK{YELLOWREDGROUNDPOWER MUSTBE SHUT OFFBLACKYELLOWREDL1L2 R Y BL1TOPUMPOHMMETERSET AT R X 1GROUNDL2{T

Page 50

Maintenance – All MotorsInsulation Resistance ReadingsThe values below are for copper conductors. If aluminum conductor drop cable is used, the resist

Page 51 - Maintenance – All Motors

Maintenance – Single-Phase Motors & Controls WARNING: Power must be on for these tests. Do not touch any live parts.A. VOLTAGE MEASUREMENTSSte

Page 52

Maintenance – Single-Phase Motors & ControlsIntegral Horsepower Control Box (Power Off)A. OVERLOADS (Push Reset Buttons to make sure contacts ar

Page 53

Maintenance – Single-Phase Motors & ControlsNOTE 1: Control boxes supplied with QD Relays are designed to operate on 230 volt systems. For 208 vol

Page 54

Maintenance – Single-Phase Motors & ControlsFOOTNOTES:(1) Lightning arrestors 150 814 902 are suitable for all control boxes. (2) S = Start, M =

Page 55 - Single-Phase Control Boxes

Maintenance – Single-Phase Motors & ControlsCAPACITOR NUMBER KIT275 463 122 305 206 912275 463 111 305 206 911275 463 120 305 206 920275 464 113

Page 56 - Ohmmeter Tests

Application – All MotorsFranklin submersible motors are designed primarily for operation in the vertical, shaft-up position. During acceleration, the

Page 57 - Table 48B Overload Kits 60 Hz

Maintenance – Single-Phase Motors & Controls1/2 - 1 hp CRC QD RELAY282 40_ 5015Sixth digit depends on hpControl Box Wiring DiagramsLINE POWERFROM

Page 58

Maintenance – Single-Phase Motors & ControlsSTARTOVERLOADLINE POWERFROM TWO POLEFUSED SWITCH ORCIRCUIT BREAKER,AND OTHER CONTROLIF USED.RELAY125 T

Page 59

Maintenance – Single-Phase Motors & ControlsSTARTOVERLOADLINE POWERFROM TWO POLEFUSED SWITCH ORCIRCUIT BREAKER,AND OTHER CONTROLIF USED. RELAYSTA

Page 60

Maintenance – Single-Phase Motors & ControlsBREAKERCIRCUITSWITCHFUSEDTWO POLEFROMPOWERLINE ORCONTROLSWITCHOR OTHERPRESSURE TO LEADGROUNDORGBLKST

Page 61

Maintenance – Electronic ProductsPumptec-PlusPumptec-Plus is a pump/motor protection device designed to work on any 230 V single-phase induction motor

Page 62

Maintenance – Electronic ProductsPumptec-PlusPumptec-Plus - Troubleshooting After InstallationSYMPTOM POSSIBLE CAUSE SOLUTIONSolid Yellow LightDry Wel

Page 63 - RUN CAPACITOR

Maintenance – Electronic ProductsQD Pumptec and PumptecQD Pumptec & Pumptec – TroubleshootingSYMPTOM CHECKS OR SOLUTIONIf the QD Pumptec or Pumpte

Page 64 - During Installation

Maintenance – Electronic ProductsThe Franklin Electric SubDrive/MonoDrive Constant Pressure controller is a variable-speed drive that delivers water a

Page 65 - After Installation

Maintenance – Electronic ProductsSubMonitorSubMonitor TroubleshootingFAULT MESSAGE PROBLEM/CONDITION POSSIBLE CAUSESF Amps Set Too HighSF Amps setting

Page 66 - QD Pumptec and Pumptec

Maintenance – Electronic ProductsSubtrol-Plus (Obsolete - See SubMonitor)Subtrol-Plus - Troubleshooting After InstallationSYMPTOM POSSIBLE CAUSE OR SO

Page 67

Application – All MotorsDistribution transformers must be adequately sized to satisfy the kVA requirements of the submersible motor. When transformers

Page 68 - SubMonitor

Maintenance – Electronic ProductsSubtrol-Plus (Obsolete - See SubMonitor)Subtrol-Plus - Troubleshooting After Installation (Continued)SYMPTOM POSSIBLE

Page 69

A Amp or amperageAWG American Wire GaugeBJT Bipolar Junction Transistor°C Degree CelsiusCB Control BoxCRC Capacitor Run ControlDI DeionizedDv/dt Rise

Page 70

Notes

Page 72

Notes

Page 73

M1311 03/07Phone Franklin’s toll free SERVICE HOTLINE for answers to your pump andmotor installation questions. When you call, a Franklin expert wil

Page 74

Application – All MotorsWARNING: To prevent accidental electrocution, automatic or manual transfer switches must be used any time a generator is used

Page 75 - TOLL FREE HELP FROM A FRIEND

Application – All MotorsFranklin Electric submersible motors are designed to operate with a cooling fl ow of water over and around the full length of t